SUN Quan, ZHANG Jie, HAN Yongxia, et al. Influence of Single Group Impulse Numbers on Aging Performance of ZnO Varistors of AC Filter Arresters[J]. High voltage apparatus, 2025, 61(6): 149-155.
DOI:
SUN Quan, ZHANG Jie, HAN Yongxia, et al. Influence of Single Group Impulse Numbers on Aging Performance of ZnO Varistors of AC Filter Arresters[J]. High voltage apparatus, 2025, 61(6): 149-155. DOI: 10.13296/j.1001-1609.hva.2025.06.017.
Influence of Single Group Impulse Numbers on Aging Performance of ZnO Varistors of AC Filter Arresters
The AC filter arresters frequently operate in use. It's core component
ZnO varistor
shows aging phenomenon in case of multiple impulse currents. While
the variation of AC/DC reference voltage and leakage current of ZnO varistor are closely related to the impulse current amplitude
impulse current waveform
number of impulses and interval time. In this regard
the variation of the AC and DC V-A characteristics of the ZnO varistor under 8/20 μs standard lightning impulse current with single group of 2 impulses and single group of 20 impulses are compared and analyzed. The test results show that for either DC V-A c
haracteristics or AC V-A characteristics
the influence of aging phenomenon of the ZnO varistor is more obvious under single group of 2 impulses than under single group of 20 impulses. In addition
when the DC reference voltage
U
1mA
drops to the value of 5%
the leakage current
I
L
at 0.75
U
1mA
is much smaller than 50 μA
namely
I
L
is deficient in characterizing the aging state of ZnO surge arresters independently;while the resistive component amplitude of the leakage current under continuous operation voltage shows linear upward trend with the number of impulse groups which
as an on-line monitoring and evaluation indicator
can well characterize the state of impulse aging
and the variation rate of it is about 70.6% when the variation rate of