Fine Modeling of Multi-cable Outgoing Lines and Calculation of Grounding Current Under Complex Working Conditions
The medium voltage power supply system of nuclear power plant contains various types of cables
with a number of up to hundreds of pieces. It involves a wide range and complex operating environment as well as high single earthing fault probability of the system. The excessive application of a large number of cables will make the capacitive current of the system exceed the standard
causing insulation fault or even arc grounding of the plant power system. There are hundreds of operating conditions of medium voltage auxiliary power system in nuclear power plant. It is in fact impossible to perform grounding current test for all operating conditions. According to the wiring diagram of auxiliary power system in a nuclear power plant in China
a refined grounding current simulation calculation model for multi-cable outgoing with more than 600 pieces of cables is set up. The maximum error between the simulated and measured values of capacitance of cable is 5.5%. Based on this model
the grounding current and system overvoltage under hundreds of operating conditions of medium voltage auxiliary power system are calculated
and the operating conditions of grounding current exceeding the standard are obtained
which can be used to guide the actual operation of nuclear power plant. Then
the real test measurement is performed on the operating conditions of the grounding current exceeding the standard
compared and verified with the simulation results. The maximum error of metal grounding is not more than 4%
and the maximum error of high resistance grounding is not more than 12%. Finally
the suppression measures for the operation conditions of the grounding current exceeding the standard is proposed
which provides a reference for the maintenance and safe operation of cable of the plant power system in the nuclear power plant.
Analysis of Three-phase Unbalance Issue of Grounding Current of Submarine and Land Cable Transition Joint
Simulation Analysis and Experimental Verification of the Three-phase Unbalance of the Grounding Current of the Submarine and Land Cable Transition Joint
Discussion on Defining the Values of Related Parameters about Grounding Project
Discussion on the Modes of Faulty Line Detection of Compensation Network
Simulation of Online Monitoring of Power Cable Insulation Using Grounding Current Method
Related Author
LIU Zongxi
CONG Yun
CAI Yong
SUN Lu
LE Yanjie
GAO Zhen
SHEN Qi
LI Jing-lu 1
Related Institution
China Electric Power Research Institute Co., Ltd.
Zhejiang Zhoushan Marine Power Research Institute Co., Ltd.
State Grid Zhejiang Electric Power Co., Ltd.
State Grid Zhoushan Electric Power Supply Company of Zhejiang Power Corporation