YANG Zheng, QIN Yan, CHEN Guang, et al. Analysis and Treatment on Abnormal Over-stroke of Contacts of High-voltage Circuit Breaker[J]. High voltage apparatus, 2025, 61(9): 209-214.
DOI:
YANG Zheng, QIN Yan, CHEN Guang, et al. Analysis and Treatment on Abnormal Over-stroke of Contacts of High-voltage Circuit Breaker[J]. High voltage apparatus, 2025, 61(9): 209-214. DOI: 10.13296/j.1001-1609.hva.2025.09.026.
Analysis and Treatment on Abnormal Over-stroke of Contacts of High-voltage Circuit Breaker
The analysis and treatment of abnormal over-stroke of 252 kV SF
6
circuit breaker is introduced in this paper. In the replacement process of operating mechanism
the fault of excessive over-stroke has been founded when measuring the contact stroke of interrupter by slow opening and slow closing operation. Such likely fault chains as operating mechanism
linkage assembly and interrupter are analyzed and the fault is confirmed in the interrupter. It is found through the disassembly analysis of the interrupter that the breakage of the moving arc contact finger is the main reason for the increase of the over-stroke. The cause of the breakage of the moving arc contact finger is analyzed by electron microscope scanning and chemical composition. The analysis and treatment of the fault have a reference for troubleshooting and treatment related to abnormal stroke of SF