Motion Behavior and Discharge Characteristics of Flake Metal Particles in GIS Under Electro-mechanical Coupling Effects
Key New Technologies for Equipment Condition Monitoring and Fault Diagnosis in New Power System Research on Fault Mechanisms of Key Power Equipment in New Power System|更新时间:2025-10-21
|
Motion Behavior and Discharge Characteristics of Flake Metal Particles in GIS Under Electro-mechanical Coupling Effects
High Voltage ApparatusVol. 61, Issue 10, Pages: 1-10(2025)
ZHAO Yingying, SI Wenrong, FU Chenzhao, et al. Motion Behavior and Discharge Characteristics of Flake Metal Particles in GIS Under Electro-mechanical Coupling Effects[J]. High voltage apparatus, 2025, 61(10): 1-10.
DOI:
ZHAO Yingying, SI Wenrong, FU Chenzhao, et al. Motion Behavior and Discharge Characteristics of Flake Metal Particles in GIS Under Electro-mechanical Coupling Effects[J]. High voltage apparatus, 2025, 61(10): 1-10. DOI: 10.13296/j.1001-1609.hva.2025.10.001.
Motion Behavior and Discharge Characteristics of Flake Metal Particles in GIS Under Electro-mechanical Coupling Effects
Flake metal particles are a common potential defect within gas-insulated switchgear (GIS)
where their motion and discharge behavior under electric fields may lead to insulation failure
thereby posing a significant threat to equipment reliability. The current studies mainly focus on particle dynamics under electric fields alone
while the influence of steady-state mechanical vibrations remains inadequately explored. In this paper a scaled GIS experimental platform capable of simultaneously applying high voltage and mechanical vibration is set up to investigate the motion patterns and discharge characteristics of flake metal particles under electro-mechanical coupling effects. Experimental results indicate that the jumping and resting characteristics of the particles are significantly influenced by their mass and shape. Particles approaching a square geometry exhibit higher jumping electric field thresholds (0.80~1.1 kV/mm)
whereas those with linear shapes demonstrate lower thresholds (0.55~0.70 kV/mm)
with the effect of vibration on the jumping threshold being negligible. The particles
once jumping
exhibit three typical motion patterns and the motion is more intense with the increase of vibration amplitude. Discharge analysis reveals that as particle mass increases,its maximum apparent discharge magnitude has evolved from a linear to an exponential relationship. Moreover,coexistance of multiple flake particles can induce chain breakdown,resulting in a denser discharge pulse pattern. These findings reveal the impact of steady-state mechanical vibration on particle motion and discharge behavior,providing an experimental basis for the assessment and mitigation of metal particle defects in GIS.
关键词
Keywords
references
SCHICHLER U , KOLTUNOWICZ W , ENDO F , et al . Risk assessment on defects in GIS based on PD diagnostics [J ] . IEEE Transactions on Dielectrics and Electrical Insulation , 2013 , 20 ( 6 ): 2165 - 2172 .
DAI Dangdang , WANG Xianpei , LONG Jiachuan , et al . Feature extraction of GIS partial discharge signal based on S-transform and singular value decomposition [J ] . IET Science Measurement &Technology , 2017 , 11 ( 2 ): 186 - 193 .
ZHANG Shuqin , ZHANG Kexuan , LUO Changlu , et al . Analysis of overvoltage and control measures at the insulation partition of GIS enclosures [J ] . Power System Protection and Control , 2025 , 53 ( 11 ): 181 - 187 .
LI Junhao , HAN Xutao , LIU Zehui , et al . Review on partial discharge measurement technology of electrical equipment [J ] . High Voltage Engineering , 2015 , 41 ( 8 ): 2583 - 2601 .
ZHANG Zhaoyu , WANG Haotian , CHEN Huan , et al . A novel IEPE AE-vibration-temperature-combined intelligent sensor for defect detection of power equipment [J ] . IEEE Transactions on Instrumentation and Measurement , 2023 ( 72 ): 1 - 9 .
ZHANG Zhaoyu , LI Junhao , SONG Yanfeng , et al . A novel ultrasound-vibration composite sensor for defects detection of electrical equipment [J ] . IEEE Transactions on Power Delivery , 2022 , 37 ( 5 ): 4477 - 4480 .
ZOU Yang , CHEN Xiaoxuan , ZHANG Yunxiao , et al . A life prediction method of transformer oil - paper insulation based oninterfacial charge polarization characteristics [J ] . Power System Protection and Control , 2024 , 52 ( 7 ): 138 - 148 .
LI Junhao , HAN Xutao , LIU Zehui , et al . A novel GIS partial discharge detection sensor with integrated optical and UHF methods [J ] . IEEE Transactions on Power Delivery , 2018 , 33 ( 4 ): 2047 - 2049 .
WANG Jian , PING An , CHANG Yanan , et al . Research on dynamic coordination of active particles suppression methods under DC stress [J ] . Transactions of China Electrotechnical Society , 2023 , 38 ( 10 ): 2794 - 2805 .
LI Qingmin , WEI Lai , XUE Naifan , et al . Research advances in visualization detection technology of micron-nano dust in AC and DCGIS/GIL [J ] . High Voltage Engineering , 2023 , 49 ( 9 ): 3607 - 3624 .
SHU Ting , YANG Yueping , GUO Ruochen , et al . Partial discharge excitation characteristics of free metal particles in SF 6 gas under AC and negative lightning impulse superposition voltage [J ] . High Voltage Engineering , 2022 , 48 ( 8 ): 3305 - 3315 .
LIU Yunpeng , HUANG Zhicheng , GENG Jianghai , et al . Selection of model for particle-insulator collision adhesion problem [J ] . High Voltage Engineering , 2022 , 48 ( 3 ): 809 - 819 .
XING Yunqi , SUN Xinbo , JIANG Jinpeng , et al . Significantly suppressing metal particle-induced surface charge accumulation of spacers in DC gas-insulated power transmission lines [J ] . Journal of Physics D-Applied Physics , 2022 , 55 ( 50 ): 504003 .
LIN Zhiyong , SU Ruohang , HUANG Guotai , et al . Evaluation of the oil-paper insulation state of a transformer based on equivalent aging capacitance [J ] . Power System Protection and Control , 2025 , 53 ( 3 ): 140 - 147 .
JIA Jiangbo , ZHA Wei , YANG Lanjun , et al . Motion behavior of spherical conducting particle around PTFE insulator under DC voltage [J ] . High Voltage Engineering , 2006 , 32 ( 11 ): 18 - 21 .
JI Hongxin . Motion behavior and discharge characteristics of metal particles in GIS under AC operating voltage [D ] . Beijing : North China Electric Power University , 2017 .
JI Hongxin , LI Chengrong , PANG Zhikai , et al . Influence of voltage waveforms on partial discharge characteristics of GIS mobilized metal particles [J ] . Transactions of China Electrotechnical Society , 2016 , 31 ( 13 ): 218 - 226 .
HU Zhiying , WEI Lai , GENG Qiuyu , et al . Firefly movement phenomenon of wire particle swarm and risk assessment in DC GIS/GIL [J ] . Proceedings of the CSEE , 2024 , 44 ( 15 ): 6219 - 6228 .
JI Hongxin , LI Chengrong , PANG Zhikai , et al . Partial discharge characteristics of freely moving flaky particles in GIS [J ] . Proceedings of the CSEE , 2017 , 37 ( 24 ): 7367 - 7376 .
HU Xinwen , LI Xiaoang , WANG Shuxiao , et al . Free metal particles movement and its induced gap breakdown characteristics in GIS under impact vibration [J ] . High Voltage Engineering , 2024 , 50 ( 1 ): 339 - 347 .
LI Zhijun , ZHANG Junjie , JIA Yang . Wide - band resonance suppressor based on adaptive active damping [J ] . Southern Power System Technology , 2024 , 18 ( 10 ): 95 - 106 .
FANG Xiang , YU Dengke , WANG Yi , et al . Suppression strategy of DC bus voltage fluctuation in hybrid microgrid based on fuzzy decoupling linear auto disturbance rejection control [J ] . Southern Power System Technology , 2024 , 18 ( 10 ): 116 - 129 .
ZHAO Shuqiang , ZHANG Hongwei , WANG Hui . Study on electrical quantities of doubly fed wind turbines considering control strategy switching during the entire low voltage ride through process [J ] . Southern Power System Technology , 2024 , 18 ( 8 ): 141 - 151 .