LIU Jun, REN Haichuan, LI Kun, et al. Analysis and Handling of a 110 kV Transformer Differential Protection Trip Incident[J]. High Voltage Apparatus, 2026, 62(1): 216-222.
DOI:
LIU Jun, REN Haichuan, LI Kun, et al. Analysis and Handling of a 110 kV Transformer Differential Protection Trip Incident[J]. High Voltage Apparatus, 2026, 62(1): 216-222. DOI: 10.13296/j.1001-1609.hva.2026.01.027.
Analysis and Handling of a 110 kV Transformer Differential Protection Trip Incident
A 110 kV transformer during operation experienced a differential protection trip
resulting in a level 3 power event characterized by a complete loss of power supply at the station. For dinding out the cause of the transformer fault
the differential protection condition
electrical test and oil chromatography data of the tranformer after the fault
with the differnce between low frequency inductance and capacitance characteristics in FRA mapping in particular are analyzed firstly
and the fault location and type of the winding are initially obtained. Then
the faulty transformer is returned to the factory for disassembly analysis.Finally
the problem-oriented design checks and mechanical strength tests of electromagnetic lines are carried out. The findings from the physical dismantling inspection of the faulty transformer windings are basically consistent with the analysis results
which verifies the correctness of the analysis method. The design verification can identify the risk of insufficient short-circuit resistance of old transformers and provide empirical guidance to prevent sudden short-circuit faults and internal fault diagnosis of transformer.
ZHA Dongjian,CHEN Wei,WU Renbiao. Comparison and analysis of diagnosis test for two high voltage station transformers after outlet short-circuit accident[J]. Transformer,2024,61(4):56-61.
WANG Mengyun. Statistics and analysis of system transformer equipment accidents in state grid corporation from 2002 to 2003(I)[J]. Power Equipment,2004(10):20-26.
电力变压器绕组变形的电抗法检测判断导则:DL/T 1093—2018[S].2018.
Guide for reactance method to detect and diagnose winding deformation of power transformer:DL/T 1093—2018[S].2018.
电力变压器绕组变形频率响应分析法:DL/T 911—2016[S]. 2016.
Frequency response analysis on winding deformation of power transformers:DL/T 911—2016[S].2016.
电力变压器第18部分:频率响应测量:GB/T 1094.18—2016[S]. 2016.
Power transformers,part18:Measurement of frequency respons:GB/T 1094.18—2016[S].2016.
LI Hongda,HUANG Dingkun,ZHANG Bin,et al. Research in detection of winding transformer variation based on improved LVI method[J]. Journal of Nanjing University of Science and Technology,2020,44(1):15-20.
LIU Liqing,MA Xiaoguang,LI Xue,et al. Study on axial vibration model and influence factors of inherent vibration characteristics of transformer winding[J]. High Voltage Apparatus,2023,59(4):149-155.
ZHENG Danyang, CHENG Yangchun, PENG Lei, et al. Construction of transfer functions and sensitivity analysis of frequency response analysis method for on - line monitoring transformer winding deformations[J]. High Voltage Engineering, 2023,49(4):1534-1544.
ZHAO Xiaozhen,YAO Chenguo,ZHOU Zehong,et al. Experimental evaluation of transformer internal fault detection based on V-I characteristics[J]. IEEE Transactions on Industrial Electronics, 2020,67(5):4108-4119.
LIU Yunpeng,LI Huan,TIAN Yuan,et al. Winding deformation detection based on distributed optical fiber sensing[J]. Transactions of China Electrotechnical Society,2021,36(7):1347-1355.
LIU Jun,CHEN She,OUYANG Zeyu,et al. Analysis and treatment of a 220 kV transformer winding deformation fault caused by single-phase grounding short-circuit[J]. Transformer, 2021,58(6):81-84.
张鑫.基于频响法的变压器绕组变形专家诊断系统[D].上海:上海交通大学,2014.
ZHANG Xin. The expert diagnosis system of transformerwinding deformation based on frequency response method[D]. Shanghai:Shanghai Jiao Tong University,2014.
SUN Xiaowei,ZHANG Yining,WANG Zhonggang,et al.Error analysis of transformer winding impedance test with low-voltage impedance method[J]. Transformer,2025,62(5):47-52.
武剑利.频响分析法检测变压器绕组变形的理论研究[D].武汉:武汉大学,2004.
WU Jianli. Study on frequency response analysis method indiagnosing transformer winding deformation[D]. Wuhan:Wuhan University,2004.
GAO Shuguo,ZHANG Yang,CHEN Zhiyong,et al. Analvsis of a 220 kV transformer windings breakage fault caused by short-circuit[J]. High Voltage Apparatus,2012,48(4):115-118.
Power transformers-Part 5:Ability to withstand short circuit:IEC 60076-5:2006[S].2006.
CIGRE Working Group 12.19. The short-circuit performance of power transformers[R]. France:CIGRE,2002.
GUO Qingtao,HUANG Xiongtao,HU Linjing. Application of transposition conductor in improving short circuit resistance of large power transformer[J]. Transformer,2010,47(1):19-22.
ZENG Huarong,LIU Jun,WU Xiangqian,et al. Comprehensive evaluation and prevention suggestions on anti - short circuit capability of 110 kV transformer in service[J]. Transformer,2019, 56(12):72-76.
ZHANG Haijun,WANG Shuhong,LI Shanshan. Analysis on cumulative effect of winding deformation of power transformer under multiple short circuits[J]. Transformer,2018,55(2):37-42.
SAHA T K. Review of modern diagnostic techniques for assessing insulation condition in aged transformers[J]. IEEE Transactions on Dielectrics and Electrical Insulation,2003,10(5):903-917.
PABLO A,PAHLAVANPOUR B. Furanic compounds analysis:A tool for predictive maintenance of oil-filled electrical equipment[J]. Electra,1997(175):9-18.
LI Zhongxiang,FU Jun,YI Meisheng,et al. Calculation and experimental study on ultimate tilt force of axial instability of transformer winding[J]. Transformer,2019,56(5):48-52.
LUO Y W,MA T,SHAO W W,et al. Effects of heat treatment on microstructures and mechanical properties of GH4169/K418 functionally graded material fabricated by laser melting deposition[J]. Materials Science&Engineering A,2021(821):141601.
LUO Yingting,XU Hailin,LIN Chunyao,et al. Transformer fault case retrieval method based on set pair analysis[J]. High Voltage Apparatus,2021,57(1):182-188.