In this paper the issue of excessive DC leakage current of 500 kV lightning arrester is studied under the non-disconnection test. As for the issue of excessive leakage current at 0.75
U
1mA
in the first section of multiple lightning arresters
a system analysis is conducted by using Ansys Maxwell simulation and on-site testing. An on-site testing plan to address this issue is proposed and it is concluded that this plan can effectively reduce the influence of ionization current on testing results and improve the accuracy of leakage current testing. The on-site test results are consistent with the simulation results.
MA Yutang,CAO Jun,QU Lu,et al.Temperature rise and failure characteristics of zinc oxide resistor for arrester considering pulse current waveform[J]. Journal of Electric Power Science and Technology,2025,40(5):306-314.
FENG Shouxin,MAO Huiqing,HU Yuanchao,et al.Lightning overvoltage and protection of distribution lines caused by lightning striking soil dissipation near buildings[J]. Insulators and Surge Arresters,2023(1):99-105.
MA Yutang,SHU Hongchun,QIAN Guochao,et al. Method for evaluating the aging state of ZnO arrester based on curve decomposition of frequency domain dielectric spectrum[J]. Transactions of China Electrotechnical Society,2024,39(3):901-913.
QIAO Xinhan,ZHANG Zhijin,JIANG Zhenglong,et al. Lightning impulse pollution flashover characteristics and model of 10 kV composite arrester combined insulator[J]. Transactions of China Electrotechnical Society,2024,39(21):6932-6940.
JIANG Nannan,WANG Wenhao,LIN Jiajun,et al.An optimal online monitoring scheme for lightening arresters based on the threephase imbalance of leakage current[J]. Zhejiang Electric Power,2024,43(5):116-124.
WANG Lili,KANG Jun,WANG Shengfu,et al. Evolution of partial discharge by needle-plate defect in oil-pressboard insulation under DC voltage[J]. High Voltage Apparatus,2023,59(2):153-161.
HE Long,ZHU Yongming,MA Jincai,et al.Analysis of influence of arrester current carrying capacity on resonant overvoltage of 220 kV transformer[J]. Transformer,2024,61(7):47-51.
LI Chunfeng,FANG Chunhua,HOU Xuanda,et al.Research on rapid live detection method of high frequency partial discharge 10 kV arrester based on k-means[J]. Electrical Measurement &Instrumentation,2024,61(7):191-196.
ZHAO Jining,LIU Xiaofei,FU Weiping,et al. Test and analysis of 220 kV MOA arrester without removing primary lead wire[J]. Hebei Electric Power,2023,42(1):80-83.
ZHANG Yunyi,MA Lei,LIU Yan,et al.Field test technique of zinc oxide arrester current balance based on IGBT series pulse power method[J]. Insulators and Surge Arresters,2022(5):79-85.
ZHANG Tianyi,LIANG Zhijian,ZHU Rui.A coupling analysis of multiphysical field for ZnO surge arrester installed in photovoltaic substation[J]. Electric Power,2022,55(9):79-87.
HU Jing,ZHANG Dunjing,ZHOU Longwu,et al. Lightning surge arrester installation strategy of UHVDC transmission line considering lightning overvoltage distribution characteristics[J]. Insulators and Surge Arresters,2022(4):177-184.
ZHANG Guohao,LI Hua,HUANG Ziqin,et al. Study on the effect of AC/DC voltage ratio on breakdown characteristics of metallized film[J]. Power Capacitor&Reactive Power Compensation,2023,44 (2):55-60.
HE Min,TANG Liang,WANG Gang,et al.Study on test method of distributed capacitance of high power reactor based on parameters separation[J]. Power Capacitor & Reactive Power Compensation, 2021,42(6):57-60.
YAO Congwei,LI Ying,PANG Xiaofeng,et al. Study and discussion on abnormal phenomenon of 10 kV dielectric loss of grading capacitor for 500 kV circuit breaker[J]. Power Capacitor&Reactive Power Compensation,2021,42(6):101-109.
WANG Shengfu,GOU Tingtao,DENG Hui,et al. Electric field intensity check and grading ring structure optimization of 2 400 kV high altitude DC voltage generator[J]. Power Capacitor&Reactive Power Compensation,2021,42(6):203-210.
LI Qian,JIANG Yudong,ZHAO Xiaofeng,et al. Simulation analysis of non-gap metal oxide surge arresters thermal breakdown caused by continuous lightning strikes[J]. Insulators and Surge Arresters,2022(5):73-78.
ZHENG Zhongyuan,LIU Guihua,JIANG Ling,et al.Calculating the spatial electric field beneath a high voltage AC transmission line by using the periodic boundary condition[J]. High Voltage Apparatus,2023,59(1):58-63.
卢文浩,肖翔,韦晓星,等.氧化锌避雷器阀片局部 U 1mA 大小与缺陷程度关系的研究[J ] .电瓷避雷器,2022(6):147-151.
LU Wenhao,XIAO Xiang,WEI X iaoxing,et al. Relationship between size of U 1mA value and defect degree of ZnO arrester valve[J ] . Insulators and Surge Arresters,2022(6):147-151.
LU Depeng,HAN Dong,HUANG Jing,et al. Temperature field simulation analysis of pole switchgear based on Ansys[J]. High Voltage Apparatus,2022,58(12):49-54.
PU Ziheng,CHEN Zhigang,SHI Xingtao,et al. Path optimization of DC field patrol inspection robot in converter station considering the influence of synthetic electric field[J]. High Voltage Apparatus, 2023,59(5):178-184.
HAN Xiaodong,CHEN Xiaodong,LI Yang,et al. Application of electrothermal coupling field analysis to electric field distribution calculation of ±800 kV wall bushing[J]. High Voltage Apparatus, 2023,59(5):35-42.
YIN Zhaoqi,XIE Pengkang,WANG Bowen,et al.Multi-physical field finite element analysis of ZnO arrester under impulse current[J]. Insulators and Surge Arresters,2023(1):216-222.