LIU Bin, ZHANG Min, WANG Qing, et al. Experimental Study on the Effect of Vibration on PZT Modulated Fiber-optic Current Transformer[J]. High Voltage Apparatus, 2026, 62(5): 132-140.
DOI:
LIU Bin, ZHANG Min, WANG Qing, et al. Experimental Study on the Effect of Vibration on PZT Modulated Fiber-optic Current Transformer[J]. High Voltage Apparatus, 2026, 62(5): 132-140.DOI: 10.13296/j.1001-1609.hva.2026.05.015.
Experimental Study on the Effect of Vibration on PZT Modulated Fiber-optic Current Transformer
PZT modulated FOCT is widely used in UHVDC projects. Sensitivity to vibration is one of the main reasons for the failure of PZT modulated FOCT. For studying the influence of vibration on PZT modulated FOCT
the vibration response test is performed to analyze the influence of different vibration excitations on different parts of FOCT. The results show that the part mostly affected by vibration in the PZT-modulated FOCT is the modulatino box
of which the delay optical fiber is the main component that causes the abnormal output of FOCT during vibration. When the external vibration affects the delay optical fiber
a non-reciprocal phase angle is generated
which superimposes the Faraday phase angle and introduces the non-reciprocal phase error. The error caused by vibration is related to the length of the optical fiber interfered by vibration
the time delay between the interference and the mirror
the vibration amplitude and the vibration acceleration. The proposed overall and local vibration response test method can effectively evaluate the vibration performance of PZT modulated FOCT. The analysis results in this paper can provide reference for the vibration test method and vibration reduction structure design of PZT modulated FOCT.
WANG Yao,ZHAO Yucan,YAN Changling,et al. Study on transient current error characteristics of optical current transformer based on closed-loop algorithm[J]. High Voltage Apparatus,2022, 58(3):148-154.
LIU Bowen,ZOU Guoping,WEI Xingchang,et al. Modeling method of high-frequency equivalent circuit of current transformer for overvoltage detection[J]. High Voltage Apparatus,2023,59 (3):156-162.
WANG Zhong,LI Zhenhua,CHENG Junjie,et al. Research on early diagnosis of fault of current transformer with Rogowski coil[J]. High Voltage Apparatus,2023,59(2):162-168.
LI Zhenhua,CHEN Xingxin,JIANG Weihui,et al. Error prediction of air-core-coil current transformer based on elastic network[J]. High Voltage Apparatus,2022,58(9):134-141.
ZHOU Lang,LIU Shuiping,YANG qian,et al.Development on explosion - proof oil - immersed current transformer[J]. Power Capacitor & Reactive Power Compensation,2025,46(1):89-97.
SUN Fan,WANG Weiqing,JIN Ming,et al.Inner insulation defect characteristic and detection method of oil immersed inverted current transformer[J]. Power Capacitor & Reactive Power Compensation,2025,46(2):120-126.
SONG Xuankun,YAN Peili,XIAO Zhihong,et al. Comment on the technology and application of fiber optic current transformer(FOCT)[J]. Power System Protection and Control,2016,44(8):149-154.
YUAN Liang,HAN Xiao,ZHENG Tuofu,et al. High speed measurement type of fiber optical current transformer[J]. Metrology & Measurement Technique,2021,48(7):83-88.
HUANG Yuhao,XIA Li,PANG Fubin,et al. Self-compensative fiber optic current sensor[J]. Journal of Lightwave Technology, 2021,39(7):2187-2193.
HUANG Yuhao,HU Bei,PENG Shen,et al. Improving the computational efficiency of birefringent model based on equivalent matrix and modified permittivity[J]. Optics Communications,2021(488):126819.
YAN Changling,LUO Sunan,WEN Jifeng,et al. Study on analysis and test of optical current transformer based on FARADAY rotation mirror[J]. High Voltage Apparatus,2022,58(2):179-184.
HU Bei,XIAO Hao,LI Jianguang,et al. Noise analysis and snr optimization design of fiber optical current transformers[J]. High Voltage Engineering,2017,43(2):654-660.
张敏杰.开环Sagnac干涉仪的数字信号处理[D]. 杭州:浙江大学,2016:12-16.
ZHANG Minjie. Digital signal processing for open-loop Sagnac interferometer[D]. Hangzhou:Zhejiang University,2016:12-16.
PANG Fubin,YUAN Yubo,DAI Feng,et al. Analysis of interference factors of all-fiber-current-transformer performance and summary of solutions[J]. High Voltage Apparatus,2022,58 (7):64-72.
Instrument transformers-Part 6:Additional general requirements for low-power instrument transformers:GB/T 20840. 6—2017[S]. 2018.
互感器第4部分:直流电流互感器的补充技术要求IEC 61869-14:2018[S].2018.
Instrument transformers - part 14:Additional requirements for current transformers for DC applications:IEC 61869-14:2018[S]. 2018.
ZHANG Hao. High temperature and vibration robustness all-fiber current sensor with a fiber-loop architecture and reflection scheme[J]. IEEE Photonics Journal,2017,9(3):1-8.
程嵩.线性双折射对全光纤电流互感器传感特性影响的研究[D]. 哈尔滨:哈尔滨工业大学,2016.
CHENG Song. The effect of linear birefringence on sensing characteristics of fiber optic current transformer[D]. Harbin:Harbin Institute of Technology,2016.
WANG Lihui,HE Zhou,LIU Xixiang,et al. Error characteristics in mutual conversion process of reflective fiber optic current transducer's optical polarization state[J]. Transactions of China Electrotechnical Society,2013,28(1):173-178.
SHI Songjie,LIU Zhanyuan,HOU Jibiao,et al. Insensitivity of fiberoptic current transducer to vibration[C]//Proceedings of Purple Mountain Forum 2019 International Forum on Smart Grid Protection and Control. Singapore:Springer Singapore,2020:497-504.
LI Xuyou,HAO Jinhui,YANG Hanrui,et al. Research on the compensating fiber loop for eliminating vibration in sagnac optic current sensor[J]. Chinese Journal of Lasers,2012,39(2):119-123.
KANG Menghua,WANG Yingli,XU Jintao,et al. Vibration immunity fiber optic current sensor employing a spun or twisted highly linear birefringence fiber[C]//Proceedings of the 32nd Chinese Control Conference. Xi'an:IEEE,2013:7468-7472.
LIU Liqing,MA Xiaoguang,LI Xue,et al. Study on axial vibration model and influence factors of inherent vibration characteristics of transformer winding[J]. High Voltage Apparatus,2023,59(4):149-155.
LIN Jing,ZHANG Jiahao,LI Xu,et al. Research on bolt looseness of high voltage circuit breaker based on vibration signal[J]. High Voltage Apparatus,2023,59(3):28-33.
LU Xiang,CHEN Xiangdong,PAN Guohong,et al. Dynamic model and seismic reinforcement analysis of transformer-bushing system[J]. High Voltage Apparatus,2022,58(9):149-156.