Study on the Influence of Plant Boundary Topography on the Noise Reduction Effect of Sound Barrier in Substations
Exploring the influence of different plant boundary topographies on the noise reduction effect of sound barriers in substations can provide a basis for the layout of sound barriers within substations
as well as a refrence for site selection of newly built substations. A 500 kV substation in Jiangsu Province is taken as an example
type AWA6228 sound level meter is used to measure the sound power levels of two transformers and a high reactor inside the substation. A multi-point equivalent source model of the transformers is constructed to predict the noise distribution in the substation. The accuracy of the developed model is verified by comparing the predicted results with the and measured data. This model is used to explore the influence of sound barrier position and height on its sound insulation performance under different terrain conditions. It is found through the Huygens Fresnel wave theory that the noise reduction effect of sound barrier is the worst on uphill terrain
and the steeper the slope
the weaker the noise barrier'a ability to block noise. In downhill terrain
the noise reduction effect is the best
and the steeper the slope
the stronger the sound barrier's ability to block noise. The conclusions in this paper can provide a reference for plant boundary topography optimization site selection for new substations.
Guo Yaoyang, Zhang Li, Hao Ying, et al. Regional short-term electricity load curve forecasting based on industry electricity consumption characteristics and multi - factor effects[J]. Power System Protection and Control,2025,53(13):82-92.
Pei Chunming, Wu Xiaowen, Hu Sheng, et al. Audible noise distribution and characteristics of a 750 kV substation[J]. High Voltage Apparatus,2016,52(1):101-105.
Wang Ying, Sun Haitao, Xue Yandeng, et al. Measurement and characteristic analysis of noise in a 750 kV substation[J]. Journal of Xi'an Polytechnic University,2019,33(5):524-530.
Li Ning, Tian Dongmei, Shan Dapeng, et al. Analysis and discussion on the noise arised from substation in city[J]. High Voltage Apparatus,2015,51(1):139-144.
Fan Xiaopeng, Li Li, Huang Chengji, et al. Analysis and control of noise pollution of an 110 kV substation[J]. Noise and Vibration Control,2014,34(5):120-124.
Tang Jinhui, Wu Fayuan, Zhi Yanli, et al. Optimization design of indoor substation ventilation and noise reduction based on deep reinforcement learning[J]. Electric Power,2023,56(1):96-105.
Ni Yuan, Wang Yanzhao, Zhou Bing, et al. Study on the influence of boundary environment of UHV substation on noise attenuation[J]. High Voltage Electrical Apparatus,2022,58(2):119-125.
Wang Chaoliang, Zhang Liangtao, Song Lizhong, et al. Predication and analysis of noise reduction of near-rail sound barriers on suburban railways[J]. Noise and Vibration Control,2022,42(6):187-191.
Zhang Chao, Liu Guoqiang, Lu Zhumao, et al. Noise interference and attenuation characteristic of UHV AC transformer[J]. High Voltage Apparatus,2022,58(10):1-7.
Ni Yuan, Zhang Jiangong, Zhou Bing, et al. Test and analysis of sound insulation performance of sound insulation cover for UHV shunt reactor[J]. High Voltage Apparatus,2021,57(2):77-83.
Zhong Sichong, Zhu Lihua, Wang Qianchao, et al. Electromagnetic vibration of power transformer and active noise reduction[J]. Transactions of China Electrotechnical Society , 2022 ,37(s1):11-21.
Yi Meisheng, Wu Hualin, Cai Wei, et al. Audible noise measurement and control technology of a 110 kV substation in residential area[J]. Smart Power,2018,46(11):83-87.
Liang Liping, Zhang Lin. Research and application of sound absorption-insulation barriers in transformer substation[J]. Chinese Journal of Environmental Engineering,2017,11(9):5326-5332.
Tian Yi, Chen Jiansheng, Liu Zhuguang, et al. Application of microporous fiber composite acoustic board in the noise control engineering of urban substations[J]. Smart Grid,2016,4(10):988-992.
Wang Suwen, Zhang Songguang, Wang Shuping, et al. Experimental study of applying a virtual sound barrier to reduce low-frequency noise of transformers[J]. Applied Acoustics ,2015 ,34(6):487-494.
吕露,汤胜,周波,等.基于多点等效模型的变压器声辐射研究[J].仪表技术,2017(5):4-7.
Lyu Lu, Tang Sheng, Zhou Bo, et al. Research on transformer acoustic radiation based on multi - point equivalent model[J].Instrument Technology,2017(5):4-7.
Hu Jingzhu, Liu Dichen, Liao Qingfen, et al. Substation noise reduction effect of barrier and analysis of influencing factors[J]. Engineering Journal of Wuhan University,2017,50(1):75-80.
HJ-2.4—2009环境影响评价技术导则——声环境[S].
HJ - 2.4—2009 Technical guidelines for environmental impact assessment-acoustic environment[S].
Pan Zhonglin. Approximate calculation of diffraction sound field of sound barrier[J]. Journal of Hangzhou University(Natural Science Edition),1987(4):426-430.
Yang Peng, Ying Liming, Wang Jinwei, et al. Reconstruction of power transformer sound field based on near-field acoustical holography[J]. Shaanxi Electric Power,2017,45(6):7-10.
Li Jiaqing, Chen Jin, Yang Chao, et al. Analysis of the impact factors on the accuracy of sound field reconstruction based on wave superposition[J]. Acta Physica Sinica,2008,57(7):4258-4264.